Fiber Optic Transfer Trip Link

Article Number: 23-450, 23-451, 23-452, 23-453


- 21-450, Multi Mode, (MM), Fiber, Binary Input, (BI):110V
- 23-451, MM, BI:220V
- 23-452, Single Mode, (SM), Fiber, BI:220V
- 23-453, SM, BI:110V


Function

The 23-45x, Fiber Optic Transfer Trip Link is intended to extend binary functions over medium and long distances. E.g. transfer trip.

The link can be delivered with fiber optic components for distances up to 80km. The protocol used by the link is designed to have high security.

The transfer trip time is around 8ms from Binary Input to Binary Output.

The link is designed for duplex mode, (2 fibers). 4 signals can be transferred in each direction. The link can also be used in simplex mode (1 fiber). Note that the remote alarm function has no relevance in simplex mode.

Every binary input is “sampled” with 25Msamples per second.

The sampled input data is filtered for changes over a period of 1ms.

The filtered input data is sent as a data message on the fiber.

In order to increase the security, for example against disturbances, the protocol on the fiber, needs 4 consecutive equal data messages before any change of the Binary output.

In addition there is a fiber optic link-control, indicating correct received data messages. This is indicated to the user by a “Link OK” – LED.

There is also a “Local alarm” – LED, and a “Local alarm” relay. (Contact open at no error). The relay and the LED are activated when an error is found. For example, at link loss.

Both the “Local Alarm”-LED and -relay has a latched function. When an error is detected in the local unit, the Local Alarm-LED is lit and the Local Alarm-relay is activated. They stay activated until the Reset alarm button is pressed.

In duplex mode, the “Local alarm” – indication is sent to the remote unit, and there indicated as “Remote alarm”.

There is one “Remote alarm” – LED, and one “Remote alarm” relay.

The Remote Alarm-LED and relay has a monostable latch function. An error detected in the remote unit will be sent to the local unit and indicated by Remote Alarm-LED and relay. When the remote unit no longer detects errors, Link-OK, Remote Alarm-LED and the relay, are inactivated. Short remote error pulses are prolonged to some seconds of time, to make sure all Remote Alarms are detectable and visualized.

Both “Local alarm” and “Remote alarm” relay outputs have the same data as for the Binary outputs.

Technical Data

Fiber optic link 23-450, 23-451 Wavelength 1300nm
Fiber optic link 23-450, 23-451 Fiber optical connector SC
Fiber optic link 23-450, 23-451 Optical system budget 10dB in multi mode 50/125µm or 62,5/125µm
Fiber optic link 23-450, 23-451 Typical distance 0-2km
Fiber optic link 23-452, 23-453 Wavelength 1550nm
Fiber optic link 23-452, 23-453 Fiber optical connector SC
Fiber optic link 23-452, 23-453 Optical system budget 31dB in single mode 9/125µm
Binary Inputs x 4 23-450, 23-453 Rated Voltage 110/125 VDC +20%. Power consumption max 0.2W/Input
Binary Inputs x 4 23-451, 23-452 Rated Voltage 220/250 VDC +20%. Power consumption max 0.2W/Input
Making capacity 30A 0.2s , 10A 1.0s
Continuous current 8A
Breaking capacity AC 250V/8A
Breaking capacity DC 48V/1A, 110V/0.4A, 250V/0.15A
Transfer Trip Time Typical <8ms
DC 48V DC to 250V DC, ±20%
AC 110VAC to 230V AC , ±20%, 50 60 Hz
AC-connector IEC 320, 3-pin
Operating Temperature Range -25 to +55°
Storage Temerature Range -40 to +85°
Relative Humidity Operating 5 to 95%
Relative Humidity Storage 5 to 95% non condensing
Immunity EN 61000-6-2
Emission EN 61000-6-4
LVD EN 50187; RIV=
Vibration IEC 60255-21-1 Class 2
Shock IEC 60255-21-2 Class 2
Seismic IEC 60255-21-3 Class 2
ESD IEC 60255-22-2 Class 3, contact 6kV, air 8kV
Radiated IEC 60255-22-3 / IEEE/ANSI C37.94.2; 35V/m
Burst Power IEC 60255-22-1 Class III
Burst Communication IEC 60255-22-1 Class II; 0,5kV diff; 1kV common mode
Fast Transient Power IEC 60255-22-4 Class IV
Fast Transient Communication IEC 60255-22-4 Class II; 1kV
Dielectric Test IEC 60255-5, 2,0kV 1min
Impuls Voltage Test IEC 60255 / EN50178 5kV / 6 kV
Insulation Resistance IEC 60255-5; > 100Mohm at 500VDC
Physical size Height 45mm, Width 483mm, Without brackets 380mm), Depth 173mm
Weight 3 kg

Features

  • Fiber optic transmission, immune to EMI and RFI
  • Standards compliant for power substation installations
  • 19" mounting with only 200mm depth
  • Single power supply range from 48VDC to 230VAC