Fiber optic IEEE C37.94-G.703 E1 multiplexer

Article Number: 21-219


- Fiber optic IEEE C37.94 G.703 E1 Multiplexer

Function

The 21-219 is an electro-optical multiplexer between one G.703/704 E1 and two IEEE C37.94 optical ports. The two IEEE ports are fully mapped into the G.704 standard frame structure of the E1 port, allowing for further SDH/PDH multiplexing and de-multiplexeing.
21-219 derives its syncronization from the network port, (E1), or from an internal 2048 kbps PDH compliant clock enabling it to be used in leased line applications using electrical E1 modems as SHDSL and alike.

IEEE C37.94

Fiber optic interface according to standard "IEEE C37.94-2002, IEEEStandard for N times 64 Kilobit per Second Optical Fiber Interfaces between Teleprotection and Multiplexer Equipment" describes a fiber optic intra-substation communication links between teleprotection equipment and multiplexers.

G.703/704 E1 Unbalanced

The ITU-standard G.703 describes the physical and electrical characteristics of hierarchical digital interfaces at rates up to 140 Mbps.
G.704 describes frame structures on G.703 interfaces up to 45 Mbps.
E1 describes a galvanic G.703 interface with G.704 frames at 2048 kbps commonly used in telecommunication.

Applications

The 21-219 Fiber Optic IEEE C37.94 - G.703 E1 Multiplexer from Fibersystem is intended for interfacing substation teleprotection equipment with IEEE C37.94 interfaces to telecom multiplexers using G.703 E1 interfaces.
The two independent IEEE C37.94 ports can be used for redundancy in the network or as a cross redundancy in dual installation.
The 21-219 Fiber optic IEEE C37.94 - G.703 converter can also be used in combination with the 21-216, (Fiber optic IEEE C37.94 - G.703 64 kbps to directly interconnect protection equipment and multiplexers to use the IEEE C37.94 standard to interconnect with equipment that only support G.703 interfaces.

Technical Data

Data Speed 2048kbps
Protocol IEEE C37.94
Fiber Multi mode 50/125µm or 62,5/125µm, ST-connector
Optical System Budget 13dB in 62,5/125µm. 9dB in 50/125µm fiber
Typical distance 0-2km (3dB system margin for 50/125µm and 6dB for 62,5/125µm)
Galvanic Data speed 2048kbps
Galvanic Protocol G.703, E1
Connector 2 x BNC , Coaxial cable
DC 48V DC to 250V DC, ±20%
AC 230V AC , ±20%, 50 60 Hz
AC-connector IEC 320, 3-pin
Operating Temperature Range -25 to +55°
Storage Temerature Range -40 to +85°
Relative Humidity Operating 5 to 95%
Relative Humidity Storage 5 to 95% non condensing
Immunity EN 61000-6-2
Emission EN 61000-6-4
LVD EN 50187; RIV=250 V OVC=III
Vibration IEC 60255-21-1 Class 2
Shock IEC 60255-21-2 Class 2
Seismic IEC 60255-21-3 Class 2
ESD IEC 60255-22-2 Class 3, contact 6kV, air 8kV
Radiated IEC 60255-22-3 / IEEE/ANSI C37.94.2; 35V/m
Burst Power IEC 60255-22-1 Class III
Burst Communication IEC 60255-22-1 Class II; 0,5kV diff; 1kV common mode
Fast Transient Power IEC 60255-22-4 Class IV
Fast Transient Communication IEC 60255-22-4 Class II; 1kV
Dielectric Test IEC 60255-5, 2,0kV 1min
Impuls Voltage Test IEC 60255 / EN50178 5kV / 6 kV
Insulation Resistance IEC 60255-5; > 100Mohm at 500VDC
Physical size Height 45mm, Width 483mm, Without brackets 380mm), Depth 173mm
Weight 3 kg

Features

  • Two independent IEEE C37.94 fiberoptical connections over a single E1.
  • Standards compliant for power substation installations
  • 19" mounting with only 200mm depth
  • Single power supply range from 48VDC to 230VAC